Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0126-00016
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/26/2026 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0126-00016 ADDRESS: (4102 E LINDEN ST TUCSON, AZ 85712) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. BRACED WALL SCHEDULE (middle of Sheet A1) a. See drawing for locations noted by symbol b. The Floor/Foundation Plan does not contain any symbol. i. Yes I do see BWA, please be consistent. Please make the necessary correction. ii. CWB 1. Is this the callout for the C-Portal Braced Wall (PFH – Portal Frame with Hold-Downs)? 2. If it is, please provide the verbiage to connect these together. 2. DETAIL 2 JOIST @ NON-BEARTING WALL a. 2X6 @ 24” O.C. i. However, it is drawn as 2x12 matching the 2x12 rafters, rim joist, & fascia. ii. Is it labeled incorrectly? iii. Please make the necessary correction. 3. DETAIL 3 NEW CONCRETE FOOTING AT EXISTING SLAB a. You are calling for special inspection for epoxy holdown. b. Will you be calling for epoxy on the dowel #4 rebar as well. If so, please add this information on the detail note. 4. Please submit for a building permit for the following: a. Prior to this permit being processed and approved, Code Enforcement CE-VIO0224-00694 i. COURT - RWOP - 1. ADU being built; 2. additional structure in rear was pool house is being utilized to live in; 3. condenser for minisplit unit and electrical box on old carport (NW side, 4. Adult Care Home (may have C of O for 10 residents). ii. A building permit is required to resolve the above code violation. This Storage permit will not be processed/approved until the above is resolved. 5. Please resubmit. |
||
| 01/12/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0126-00016 (4102 E LINDEN ST TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). 1. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor size/type and conduit size/type. Note wet use requirements and burial depth. NEC arts;300 and 408.4. 2. Provide a disconnecting means at each building where the branch circuits or feeders enter the buildings, per NEC 225.31 3. Provide a grounding electrode system at the new structure per NEC 250.32. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/09/2026 | Site Engineering | REQUIRES RESUBMIT | Site Engineering Review TC-COM-0126-00016 4102 E LINDEN ST Summary: Storage room Site Engineering comments are as follows: 1. This proposed commercial building permit will require a Development Package that complies with the criteria found in Administrative Manual 2-06.4.0 thru 2-06.4.9. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8794 2. This project lies within the boundaries of the Alvernon Wash floodplain. A floodplain use permit (FPU) will be required for both permits. Please start a new FPU with elevation certificate under the sub-records tab of this permit on the Tucson Development Center Portal: https://tdc-online.tucsonaz.gov/#/home 3. The structure must be elevated to the regulatory flood elevation or flood-vented floor compliance. a. If elevated, the finished floor elevation (FFE) of the structure shall be at or above 2461.8-ft North American Vertical Datum 1988 (NAVD88). b. If flood venting is opted for, the vents shall be installed in at least two different walls of the structure. The bottom of the vents shall be no higher than 12-in above grade. The total size of venting shall be a minimum of 360 square inches. (Vent 1 + Vent 2 = 360 square inches or more). To re-submit, visit the Tucson Development Center Online at: https://tdc-online.tucsonaz.gov/#/home The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 01/21/2026 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0126-00016 4102 E. Linden St. Tucson, AZ 85712 Storage Room (1st Review) TRANSMITTAL DATE: 1/21/2026 This site is located in the R-1 zone (UDC 4.7.8). Adult Care Services is an allowed use in the zone (UDC Table 4.8-2) subject to Use Specific Standards 4.9.7.J.2.a, 3.a, and 4. Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the minimum requirements is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/submittal_requirements.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers. 2. Comment: Please clarify why the current use is listed as Single Family Residential under property info however in the footprint of the house references the use as “existing assisted residence”? 3. Comment: Per UDC 6.6.3.C, “Detached accessory buildings, including accessory dwelling units, are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line, except for shade structures or carports not over 400 square feet in floor area, terraces and steps not over three feet high above natural grade, paved areas, and fences or walls”. Please either demonstrate that these requirements are met, or a Board of Adjustment Variance will be required if you do not meet these requirements. Please reach out to Mark Castro at Mark.Castro@tucsonaz.gov if you have questions about the Board of Adjustment Variance process. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration#section-2. 4. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 01/21/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 01/07/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |