Permit Number: TC-COM-0125-00203
Parcel: 13355231B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0125-00203
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2025 Site Engineering Fast NOT REQUIRED
02/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0125-00203 (9615 E OLD SPANISH TR TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

General:
1. A signature and date are required as part of the Registrant Seal (Electrical). Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed. >>> Seal is missing signature and date signed.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/06/2025 Commercial Mechanical Fast REQUIRES RESUBMIT 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration states that in addition to signing the seal, the registrant shall include the date the document was sealed.
2. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
02/04/2025 PDSD Application Completeness Express REVIEW COMPLETED