Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0125-00202
Parcel: 132131390

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0125-00202
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/21/2025 6:55:36 PM
03/26/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/26/2025 9:55:24 AM
03/26/2025 Outdoor Lighting Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/21/2025 6:55:36 PM
04/14/2025 Water - PDSD Standard APPROVED
04/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 3/20/2025 6:48:07 PM
1. (RESOLVED) - General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED agency is acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements.
2. (UNRESOLVED) - General - Provide Heat Load Calculations. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
i. Plan Sheet M005 - FCU2/HP2 system Checksums - Net Total 8876 BTU/h. - Plan Sheet M001 - states on the Total Capacity (MBH) 24.0 (24000 BTU/h). - The output capacity of heating and cooling equipment shall be not greater than that of the smallest available equipment size that exceeds the loads calculated in accordance
with Section C403.1.1. - 2018 IECC - C403.3.1 Equipment sizing (Mandatory).
3. (RESOLVED) - Plan Sheet M002 - Detail #3 states on detail for Guest Laundry, PROVIDE MOTERIZED DAMPER INTREGAL WITH EXTERIOR LOUVER. (TYP.). Provide size for O/A Makeup Louver. Substantiate with calculations. - 2018 IMC Section 504.6 Makeup air.
04/08/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0125-00202
1680 E TUCSON MARKETPLACE BL

The building permit cannot be approved until the associated development package, TD-DEV-0125-00003, is approved.
04/04/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: Zoning Review Section

PROJECT: TC-COM-0125-00202 - TD-DEV-0125-00003
1680 E TUCSON MARKETPLACE BL – PAD-15
Travelers Accommodation, Lodging (2nd Review)

TRANSMITTAL DATE: April 4, 2025

This site is located in PAD-15, Travelers Accommodation, Lodging is an allowed use in the PAD.

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has reviewed the Hotel plans for compliance with Development Package (DP) TD-DEV-0125-00003 and all though the plans appear to match until the DP is approved by all review agencies Zoning cannot approve this permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/19/2025 PDSD Application Completeness Express REVIEW COMPLETED