Permit Number: TC-COM-0125-00196
Parcel: 11449036C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0125-00196
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2025 Commercial Building APPROVED
02/19/2025 Site Zoning APPROVED
02/13/2025 Water - PDSD APPROVED
02/04/2025 Outdoor Lighting NOT REQUIRED No outdoor lighting changes.
02/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/04/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0125-00196 (8625 E TANQUE VERDE RD TUCSON, AZ 85749)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
2. Provide a panel schedule showing the circuits that are being modified.
3. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/13/2025 Commercial Mechanical REQUIRES RESUBMIT Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to the restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
02/13/2025 Commercial Plumbing REQUIRES RESUBMIT Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for ½” pipe).
02/05/2025 Fire New Construction REVIEW COMPLETED
02/03/2025 PDSD Application Completeness Express REVIEW COMPLETED
02/18/2025 Site Engineering REVIEW COMPLETED