Permit Number: TC-COM-0125-00195
Parcel: 11628001L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00195
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2025 Site Zoning Standard APPROVED
02/21/2025 Site Landscape Standard NOT REQUIRED
03/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2025 Commercial Building Standard REQUIRES RESUBMIT February 7, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS GUEST SUITES
REMODEL

City of Tucson Permit Number: TC-COM-0125-00195
Stantec Project Number: 185215066
Stantec File Number: TUC-25-022

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 31,549 158 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.6

1. Please provide the listed fire-rated assembly for wall type C fire partition. [Ref. IBC 2018 Sec. 703.3]


Sheet A2.7

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.8

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.9

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.10

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.11

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.


PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations due to the increase in plumbing fixtures. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/17/2025 Commercial Electrical Standard REQUIRES RESUBMIT February 7, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS GUEST SUITES
REMODEL

City of Tucson Permit Number: TC-COM-0125-00195
Stantec Project Number: 185215066
Stantec File Number: TUC-25-022

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 31,549 158 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.6

1. Please provide the listed fire-rated assembly for wall type C fire partition. [Ref. IBC 2018 Sec. 703.3]


Sheet A2.7

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.8

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.9

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.10

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.11

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.


PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations due to the increase in plumbing fixtures. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/17/2025 Commercial Mechanical Standard REQUIRES RESUBMIT February 7, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS GUEST SUITES
REMODEL

City of Tucson Permit Number: TC-COM-0125-00195
Stantec Project Number: 185215066
Stantec File Number: TUC-25-022

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 31,549 158 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.6

1. Please provide the listed fire-rated assembly for wall type C fire partition. [Ref. IBC 2018 Sec. 703.3]


Sheet A2.7

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.8

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.9

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.10

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.11

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.


PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations due to the increase in plumbing fixtures. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/17/2025 Commercial Plumbing Standard REQUIRES RESUBMIT February 7, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS GUEST SUITES
REMODEL

City of Tucson Permit Number: TC-COM-0125-00195
Stantec Project Number: 185215066
Stantec File Number: TUC-25-022

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-1 I-B 31,549 158 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A2.6

1. Please provide the listed fire-rated assembly for wall type C fire partition. [Ref. IBC 2018 Sec. 703.3]


Sheet A2.7

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.8

1. The plans indicate a recessed niche proposed in the fire-rated partition separating sleeping units. Please provide a listed-fire rated assembly that will maintain the required 1-hour separation with the reduced wall width in that area. [Ref. IBC 2018 Sec. 703.3]

Sheet A2.9

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.10

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

Sheet A2.11

1. The proposed wall type D indicated for the corridor/sleeping unit common wall is not rated. The corridor walls are required to be fire partitions with a minimum fire rating of 30 minutes. Please revise and provide a listed fire-rated assembly. [Ref. IBC 2018 Sec. 1020.1}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.


PLUMBING COMMENTS

General

1. Please provide updated water pressure calculations due to the increase in plumbing fixtures. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/10/2025 Fire New Construction Standard REVIEW COMPLETED Fire alarm and fire sprinklers upgrades will required a separate permit.
02/01/2025 PDSD Application Completeness Express REVIEW COMPLETED
02/24/2025 Site Engineering Standard REVIEW COMPLETED