Permit Number: TC-COM-0125-00181
Parcel: 133180010

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0125-00181
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2025 Site Zoning APPROVED
02/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/14/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet A3.0: Please provide dimensioned drawings and details for the ramp handrails to include attachment details and required handrail extensions as well as being able to resist a linear load of 50 pounds per linear foot and a concentrated load of 200 pounds. IBC 107.2.1 & IBC 1012.8 & IBC 1607.8
2. Sheet A3.0: Please amend the plans (Section A and B) to call out the minimum depth of the column footings below the undisturbed ground surface as 12 inches. IBC 1809.4
3. Sheet A3.0: Please amend the plans to call out type of epoxy and ½ inch bolts to be used for Detail 1/A3.0
4. Structural Calcs: Amend the calculations to include a design criteria to include structural design information as indicated in IBC 1603.1 Please note wind speed has been amended by the City of Tucson.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/05/2025 Fire New Construction REVIEW COMPLETED
02/01/2025 PDSD Application Completeness Express REVIEW COMPLETED
02/14/2025 Site Engineering REVIEW COMPLETED