Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0125-00170
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/17/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please submit dimensioned architectural site plan and construction drawings prepared by an Arizona licensed design professional for this project. IBC 1017.2. 2. Please see City of Tucson Commercial submittal requirements - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 03/27/2025 | Site Engineering | REQUIRES RESUBMIT | See comments from Site Zoning and Commercial Building. | ||
| 03/18/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0125-00170 - TD-DEV-0223-00141 1109 W GLENN ST. - I-1 6 space covered parking structure (2nd Review) TRANSMITTAL DATE: March 18, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the I-1 zone (UDC 4.7.29). Construction Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.Q with and accessory use of Hazardous Material Storage subject to Use Specific Standards 4.9.10.B.1 & 2.d. 1. Until the revision to the DP is approved by all review agencies Zoning cannot approve this plan. The proposed covered parking structure is not shown on development package (DP) TD-DEV-0223-00141 and a revision to the approved DP is required prior to approval of this permit. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 03/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |