Permit Number: TC-COM-0125-00150
Parcel: 119215930

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00150
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2025 Site Zoning Standard APPROVED
02/19/2025 Water - PDSD Standard APPROVED
02/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2025 Commercial Building Standard REQUIRES RESUBMIT February 4, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00150
Stantec Project Number: 185215066
Stantec File Number: TUC-24-021

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,966 45 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, EFIS.

ARCHITECTURAL COMMENTS

General

1. Sheet ED1.0 indicates that the existing fire alarm is to be relocated. Does this building have a fire alarm installed? If so, please indicate that the modification of the fire alarm system will be provided as a separate submittal on the cover page. If not, please have this note removed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

3. Please indicate the ESR or Intertek testing number for the proposed E.I.F.S system. [Ref. IBC 2018 Sec. 1703.4.2]

STRUCTURAL COMMENTS

General

1. Please provide the structural calculations for the engineered structural design. [REF. IBC 2018 Sec. 107.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. Please indicate an exit sign above the work area/circulation door. [Ref. IBC 2018 Sec. 1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Electrical Standard REQUIRES RESUBMIT February 4, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00150
Stantec Project Number: 185215066
Stantec File Number: TUC-24-021

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,966 45 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, EFIS.

ARCHITECTURAL COMMENTS

General

1. Sheet ED1.0 indicates that the existing fire alarm is to be relocated. Does this building have a fire alarm installed? If so, please indicate that the modification of the fire alarm system will be provided as a separate submittal on the cover page. If not, please have this note removed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

3. Please indicate the ESR or Intertek testing number for the proposed E.I.F.S system. [Ref. IBC 2018 Sec. 1703.4.2]

STRUCTURAL COMMENTS

General

1. Please provide the structural calculations for the engineered structural design. [REF. IBC 2018 Sec. 107.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. Please indicate an exit sign above the work area/circulation door. [Ref. IBC 2018 Sec. 1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT February 4, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00150
Stantec Project Number: 185215066
Stantec File Number: TUC-24-021

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,966 45 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, EFIS.

ARCHITECTURAL COMMENTS

General

1. Sheet ED1.0 indicates that the existing fire alarm is to be relocated. Does this building have a fire alarm installed? If so, please indicate that the modification of the fire alarm system will be provided as a separate submittal on the cover page. If not, please have this note removed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

3. Please indicate the ESR or Intertek testing number for the proposed E.I.F.S system. [Ref. IBC 2018 Sec. 1703.4.2]

STRUCTURAL COMMENTS

General

1. Please provide the structural calculations for the engineered structural design. [REF. IBC 2018 Sec. 107.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. Please indicate an exit sign above the work area/circulation door. [Ref. IBC 2018 Sec. 1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Plumbing Standard REQUIRES RESUBMIT February 4, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00150
Stantec Project Number: 185215066
Stantec File Number: TUC-24-021

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,966 45 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, EFIS.

ARCHITECTURAL COMMENTS

General

1. Sheet ED1.0 indicates that the existing fire alarm is to be relocated. Does this building have a fire alarm installed? If so, please indicate that the modification of the fire alarm system will be provided as a separate submittal on the cover page. If not, please have this note removed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

3. Please indicate the ESR or Intertek testing number for the proposed E.I.F.S system. [Ref. IBC 2018 Sec. 1703.4.2]

STRUCTURAL COMMENTS

General

1. Please provide the structural calculations for the engineered structural design. [REF. IBC 2018 Sec. 107.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. Please indicate an exit sign above the work area/circulation door. [Ref. IBC 2018 Sec. 1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Outdoor Lighting Standard REQUIRES RESUBMIT February 4, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00150
Stantec Project Number: 185215066
Stantec File Number: TUC-24-021

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,966 45 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, EFIS.

ARCHITECTURAL COMMENTS

General

1. Sheet ED1.0 indicates that the existing fire alarm is to be relocated. Does this building have a fire alarm installed? If so, please indicate that the modification of the fire alarm system will be provided as a separate submittal on the cover page. If not, please have this note removed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

3. Please indicate the ESR or Intertek testing number for the proposed E.I.F.S system. [Ref. IBC 2018 Sec. 1703.4.2]

STRUCTURAL COMMENTS

General

1. Please provide the structural calculations for the engineered structural design. [REF. IBC 2018 Sec. 107.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. Please indicate an exit sign above the work area/circulation door. [Ref. IBC 2018 Sec. 1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/05/2025 Fire New Construction Standard REVIEW COMPLETED
01/31/2025 PDSD Application Completeness Express REVIEW COMPLETED
02/24/2025 Site Engineering Standard REVIEW COMPLETED