Permit Number: TC-COM-0125-00133
Parcel: 10707003D

Address:
1109 W GLENN ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0125-00133
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2025 Commercial Building APPROVED
02/03/2025 Commercial Electrical APPROVED
02/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2025 Site Engineering REQUIRES RESUBMIT 1. This fueling station is not shown in the approved development package TD-DEV-0223-00141. Please add this to the scope of work under revision 3 which is currently awaiting resubmittal.

Mike Ortiz
michael.ortiz@tucsonaz.gov
02/12/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0125-00133 - TD-DEV-0223-00141
1109 W GLENN ST. - I-1
Above ground fuel storage tank and dispensing system (1st Review)

TRANSMITTAL DATE: ‎February 12, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 zone (UDC 4.7.29). Construction Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.Q with and accessory use of Hazardous Material Storage subject to Use Specific Standards 4.9.10.B.1 & 2.d.

1. The proposed ground fuel storage tank and dispensing system is not shown on development package (DP) TD-DEV-0223-00141 is will be required to be on the approved DP prior to approval of this permit.

2. Per :Use Specific Standard 4.9.10.B.2.d the maximum capacity allowed is a 10,000 gallons tank. Based on Keynote 11A on sheet A1.2 you are proposing a 17,280-gallon tank. A Board of Adjustment for Variance will be required to allow the larger tank. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/04/2025 Fire New Construction REVIEW COMPLETED The proposed project requires a separate operational permit, please contact Jesus.sila@tucsonaz.gov for additional Information
01/29/2025 PDSD Application Completeness Express REVIEW COMPLETED