Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0125-00098
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2025 | Commercial Electrical | APPROVED | |||
02/03/2025 | Site Zoning | APPROVED | |||
01/30/2025 | Water - PDSD | APPROVED | |||
01/27/2025 | Commercial Building | NOT REQUIRED | |||
01/30/2025 | Commercial Mechanical | NOT REQUIRED | |||
01/28/2025 | Outdoor Lighting | NOT REQUIRED | no changes to the outdoor lighting. | ||
02/04/2025 | Site Engineering | NOT REQUIRED | |||
02/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/30/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Appliances (e.g. beverage dispensers, smoothie machines, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018. | ||
01/22/2025 | Fire New Construction | REVIEW COMPLETED | |||
01/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |