Permit Number: TC-COM-0125-00092
Parcel: 110160560

Address:
6137 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-0125-00092
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2025 Commercial Electrical APPROVED
05/16/2025 Commercial Mechanical APPROVED
05/16/2025 Commercial Plumbing APPROVED
05/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2025 Commercial Building REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.
COMMENTS:
Comments were not addressed and plans state PRIVATE BATHROOM; however, Each toilet room and bathing room shall be accessible per IBC 1109.1 with an exception #1. Toilet rooms or bathing rooms accessed only through a private office, not for common or public use and intended for use by a single occupant, shall be permitted to comply with the specific exceptions in ICC A117.1. This bathroom does appear to meet the requirements of a private bathroom and therefore must be shown as Accessible. Please address the comments below and provide interior elevations and an enlarged floor plan of the bathroom with all required dimensions, draw clear floor spaces on the plans, etc. IBC 107.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov


1. Sheet A1: Floor Plan a. LAVATORY & SINK
i. Provide clear floor space for sink. ICC A117.1 606.2. Lavatories & sinks shall be 34 inches maximum above the floor, measured to the higher of the rim or counter surface per ICC A117.1 606.3
ii. Lavatory faucet operator shall also be metered. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. b. WATER CLOSET
i. At water closet, show the 60" W x 56" D clearance area on the floor per ANSI A117 Figure 604.3 Ensure no other fixtures are within this area.
ii. Grab bars ICC ANSI A117.1 section 604.5, toilet and bathing facilities, grab bars and shower seat reinforcement sec 1104.11 ICC A117.1
2. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/02/2025 PDSD Application Completeness Express REVIEW COMPLETED