Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00089
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/28/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide an electronic version of the drawings or a higher resolution scanned version of the drawings as these are not legible. INC 107.2.1
2. Please review City of Tucson Commercial Submittal Requirements and include missing information. IBC 107.2.1 for example.
3. Site plan indicating the area where work is to be conducted.
4. Structural Calculations used in the design of this repair.
5. Please see Electronic Drawing Standards for Submitted Plans:
• All Documents shall be in PDF format, with a graphic scale, and rotated so pages
read upright.
• Verify you have unlocked and flattened all the drawings and reports.
• Sheet title block sizes and locations shall remain constant on each page of the plan set.
• Reserve the same location, minimum size of 3”x 5”, on all plan sheets for City stamps.
• Files shall only be saved in black and white.
• Documents, drawings, and reports must be submitted as a separate PDF for
each document type (i.e. plans, calculations, specifications, application, etc.)
Building Plan Requirements, etc see below link

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/05/2025 Site Engineering Standard REQUIRES RESUBMIT see zoning comment
02/04/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0125-00089
425 W PASEO REDONDO – C-3
Covered parking structures (1st Review)

TRANSMITTAL DATE: February 4, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

The site is in the C-3 zone (UDC 4.7.22). Multifamily is an allowed use in the zone (UDC Table 4-8-4)

1. As this site is located within the COT Downtown Core and Rio Nuevo Area (RNA) RNA review must be completed and approved prior to approval of this building permit. RNA requirements can be found at; https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Special-Districts. Contact Maria Gayosso at (520) 837-6972 or email Maria.Gayosso@tucsonaz.gov with questions regarding the RNA review.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/14/2025 Fire New Construction Standard REVIEW COMPLETED
01/14/2025 PDSD Application Completeness Express REVIEW COMPLETED