Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0125-00075
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/13/2025 | Commercial Mechanical Fast | REQUIRES RESUBMIT | “Connecting to the existing ductwork” ..., does not mean that there will be adequate ventilation (i.e. outside air). Ventilation for R-2, R-3, and R-4 occupancies, “shall be provided by an exhaust system, supply system (e.g., an outside air inlet) or a combination thereof.” See Sections 403.3.2.1 through 403.3.2.5, IMC 2018 for further information on ventilation requirements. [Second comment: Comment not addressed; provide a written response to the comment.] [Initial comment: Show how mechanical ventilation is being provided. Reference: Section R403.6 and R503.1.2, IECC 2018.] | ||