Permit Number: TC-COM-0125-00074
Parcel: 130141610

Review Status: Requires Resubmit

Review Details: COMMERCIAL FENCE/WALL v.1

Permit Number - TC-COM-0125-00074
Review Name: COMMERCIAL FENCE/WALL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/24/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please dimension the height and width of the gates and posts on the plans. INC 107.2.1
2. Provide dimensions from the property line to the gate. IBC 107.2.1
3. Provide a drawing for the gate post construction and indicate the material types and sizes to be used with this project. IBC 107.2.1 For example are the posts metal? if so what size and thickness are the metal posts ?

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/29/2025 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-0125-00074 (1524 S COLUMBUS BL TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide electrical load calculations, for the Main Service Panel and sub-panels, Per NEC 220.40.
2. Show the location of the new sub-panel(B) on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A)


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/30/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0125-00074
1524 S COLUMBUS BL. – R-3
New Entry gate system – Multifamily Condos (1st Review)

TRANSMITTAL DATE: January 30, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.12). A multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/27/2025 Fire New Construction REVIEW COMPLETED 503.6 Security gates. ( 2018 IFC)
The installation of security gates across a fire apparatus access road shall be approved by the fire code official. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. Electric gate operators, where provided, shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed and installed to comply with the requirements of ASTM F2200.
Add A Knox Override key switch to electric gates for fire department access.
01/16/2025 PDSD Application Completeness Express REVIEW COMPLETED
01/31/2025 Site Engineering REVIEW COMPLETED