Permit Number: TC-COM-0125-00049
Parcel: 11619201C

Address:
2 N FREEWAY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0125-00049
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2025 Fire New Construction NOT REQUIRED
01/13/2025 Outdoor Lighting NOT REQUIRED No lighting or electrical under this permit. Any electrical or lighting shall require a separate permit.
01/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/21/2025 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/21/2025 7:03:12 AM
1. General: Provide the geotechnical engineer report, loads and codes, plans, and calculations used for this project. (2018 IBC sections 107, 1803)





Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/21/2025 7:00:44 AM
1. General: Provide the Special Inspections Intermediate Certificate with parts A & B completed for verification of the approved Special Inspectors for the special inspections required. (City of Tucson required submittal, 2018 IBC
Chapter 17, section 1704.2.1)
2. General: Provide the scope of work for the proposed project under this permit. The cover sheet is for the main building and lists numerous sheets that are not included in the set. (2018 IBC section 107)
3. General: Include the plans, calculations, building data, elevation views of all sides, if sprinklers or fire alarms are being installed, foundation and structural plans, etc. specific to this project. The Project details applied for state a fuel canopy and but only drawings provided are for a trash enclosure. (2018 IBC section 107)
01/21/2025 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/21/2025 7:02:06 AM
1. General: Provide the electrical scope of work and plans. Include the hazardous classification and show the classified areas and all electrical details. (2018 IBC section 107), 2017 NEC Article 500)
01/22/2025 Site Engineering REQUIRES RESUBMIT TC-COM-0125-00049
2 N FREEWAY

Site engineering comments are as follows:
1. The associated development package, TD-DEV-0723-00337, must be approved by all reviewers prior to the approval of this permit submission. UDC Article 3.3.3.7.a
Ryan Insalaco – ryan.insalaco@tucsonaz.gov