Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0125-00007
Parcel: 11619185F

Address:
252 N MELWOOD AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0125-00007
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2025 Bldg Permits - Post Review PENDING ASSIGNMENT
01/09/2025 Commercial Mechanical REQUIRES RESUBMIT 1. The manufacturer’s literature indicates that the nominal energy efficiency range of the proposed condensing unit (Goodman GLXS4B) is 13.8 to 14.5 SEER2, depending upon the evaporator coil used. Split-system air conditioners that do not meet the new M1 Standards published by the Department of Energy cannot be installed after January 1, 2023. The new 2023 Standards for units <45,000 BTUH are 14.3 SEER2 which is equivalent to 15 SEER. Verify that the proposed split system will have a minimum energy efficiency of 14.3 SEER2.
2. The submitted Manual J heating/cooling loads show a sensible cooling load of 22,877 BTUH and an equipment total cooling load of 22,996 BTUH. The expanded cooling data for the proposed split system (105F outdoor air, 80F IDB, 67F IWB and 800 CFM) shows a sensible cooling capacity of only 17,710 BTUH. In addition, the Manual J calculations show a required total capacity of 2.7 tons at 0.70 SHR. The proposed split system is under-sized.
3. Show how mechanical ventilation is being provided. Reference: Section R403.6 and R503.1.2, IECC 2018.
01/02/2025 PDSD Application Completeness REVIEW COMPLETED