Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0124-00219
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2024 | Commercial Plumbing | APPROVED | |||
| 02/26/2024 | Site Zoning | APPROVED | |||
| 03/07/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please indicate on the electrical plans the scope of work in detail, or show what is new and what is existing to remain. 2 Also be advised that the electrical panel cannot be located in a closet. Please locate the panel to a code compliant location. NEC 240.34(D),(E), and 408.17. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 03/07/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show the location of EF-2 and note the required ventilation exhaust flow rate. Reference: Section 403.3.2.1, IMC 2018. 2. The equipment specs refer to a clothes dryer exhaust. Does this exhaust exist? Reference: Section 107.2.1, IBC 2018. 3. Clarify Demolition Plan Keynote #3 on sheet D1.0. Reference: Section 107.2.1, IBC 2018. |
||
| 03/07/2024 | Commercial Structural | REQUIRES RESUBMIT | TC-COM-0124-00219 (2950 N ALVERNON WY Unit:5106 TUCSON, AZ 85712) Restoration due to water damage. Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Sheet T0.0: Please amend Summary of Governing Codes to replace Pima County Zoning Code with a reference to City of Tucson, and please add International Existing Building Code. IBC 107.2.1 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
| 02/27/2024 | Site Engineering | REQUIRES RESUBMIT | This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://tdc-online.tucsonaz.gov/#/home NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TIs and solar). Instructions: 1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record 2. Locations -> Confirm the location is accurate to the project. Click “Next” 3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next” 4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next” 5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next” 6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next” 7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next” 8. Review and Submit -> Review all information to ensure accuracy. Click “Submit” Contact Lianne Evans at lianne.evans@tucsonaz.gov or Stephen Blood at Stephen.Blood@tucsonaz.gov if you have any questions about the FUP. |
||
| 02/05/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 02/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |