Permit Number: TC-COM-0124-00198
Parcel: 119180910

Address:
3776 S 16TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0124-00198
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/15/2024 Commercial Mechanical REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Mechanical Review Section comments were addressed. In accordance with SECTION 107 of the 2018 IBC and the PDSD Building Plan Requirements:

1. Provide a roof plan showing where the Roof Top Units are located. IBC 107.2
2. Provide an provide an engineering evaluation from an Arizona registered engineer to indicate the existing roof structure can support the new RTU to include calculations, plans/details for the support of such equipment. IBC 107.2 Alternatively, provide the weight of existing RTU to be removed and a comparison to the new RTU’s weight. If the new RTU weighs less than the existing, removed RTU all is good.
3. Provide a complete Set of Heating/Cooling Load Calculations. The load calculations must be sealed a design professional registered in Arizona. IMC 312 (Cool Calc and Manual J are for residential applications)
4.Provide an equipment schedule to include all equipment listings, specifications and weights IMC 301.
5. Provide condensate drain line size type and terminations. IMC 307
6. Provide Ventilation Calculations Provide calculations according to 2018 IMC 401, 402, 403, Table 403.3.
7. Provide air balance schedule IMC 403, 501.4
8. Provide Energy Code Calculations Provide calculations (COMcheck) according to 2018 IECC C403

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
01/30/2024 PDSD Application Completeness REVIEW COMPLETED