Permit Number: TC-COM-0124-00191
Parcel: 117060210

Address:
605 E 9TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0124-00191
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/12/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Show the location of the reduced pressure backflow assembly on the drawings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatory in the restroom adjacent to the gym complies with the requirements of Section C404.5, IECC 2018.
3. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (see B/P-0, D/P-0, F/P0, and G/P-0). Reference: Section 704.3, IPC 2018.
02/22/2024 PDSD Application Completeness REVIEW COMPLETED