Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0124-00191
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/12/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Show the location of the reduced pressure backflow assembly on the drawings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatory in the restroom adjacent to the gym complies with the requirements of Section C404.5, IECC 2018. 3. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (see B/P-0, D/P-0, F/P0, and G/P-0). Reference: Section 704.3, IPC 2018. |
||