Permit Number: TC-COM-0124-00184
Parcel: 14041867A

Address:
3350 E WESTCO PL

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0124-00184
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
03/20/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 3/19/2024 9:26:29 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/5/2024 12:07:58 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/6/2024 2:30:26 PM
1. General - Add to Cover Sheet The Conveyer System conforms to 2018 IBC Chapter 30 - Elevators and Conveying
Systems - Section 3004 and ASME B20.1 - (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/5/2024 10:01:22 AM
Electrical Review of FedEx
By: Ron Ross PE
A2422-PER101: Comment only: 2, 3, and 5 Hp motors all seem to be overloaded for 480V motors.

A2422-PER401: Should have shown Panel PDP2 and indicate motor/vfd locations. Fortunately, Sheets ED1.3 and ED1.5 do show locations. If this information had not been provided, the electrical application would have been denied



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/7/2024 12:22:00 AM
Second Plumbing Review: No Plumbing Work shown
Resolved-1). Need to address Building Plan Review comment #1 -2018 IPC 403.1
03/18/2024 PDSD Application Completeness Express REVIEW COMPLETED