Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0124-00184
Parcel: 14041867A

Address:
3350 E WESTCO PL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00184
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2024 Site Zoning APPROVED
02/27/2024 Site Engineering NOT REQUIRED
02/27/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/15/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 2/12/2024 8:47:53 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.

2. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be
downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf

3. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. The construction documents must indicate the name and registration number of the engineering firm by which the signing engineer is employed. Please update the construction documents to comply with this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information.

4. CURRENT CODE: The currently adopted building code for the City of Tucson is the 2018 International Building Code and its auxiliary codes. Please update the structural drawings to comply with the 2016 version of ASCE 7.

5. STRUCTURAL CALCULATIONS - SEISMIC DESIGN CATEGORY: The structural general notes, ED1.2, do not match the seismic design information on Page 2 of 43 of the structural calculation package. The general notes indicate that this project is classified as seismic design category D, while the calculations include the lines, "The attached data and analysis is valid for projects in Seismic Design Category A and B", and "The seismic design parameters for the worst case seismic loads for Seismic Design Category C were used to calculate seismic loads for this project".
Further, the spectral accelerations, Ss and Sds are inconsistent between the general notes and the calculations. Please verify the seismic design criteria and resubmit, resolving these contradictions.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 2/6/2024 2:36:46 PM
1. General: Provide a basic code analysis for permitting. Provide the occupancy use, area of work, occupant load, construction type, the existence of sprinklers and alarms.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/12/2024 9:41:15 PM
1. General - Add to Cover Sheet The Conveyer System conforms to 2018 IBC Chapter 30 - Elevators and Conveying Systems - Section 3004 and ASME B20.1




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 1/31/2024 11:50:33 AM
Electrical Review
By: Ron Ross PE
Submittal does not include any electrical.
If an electrical permit is required, electrical drawings will need to be submitted.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/15/2024 1:27:17 AM
First Plumbing Review:
1). Need to address Building Plan Review comment #1 -2018 IPC 403.1
02/26/2024 Fire New Construction REQUIRES RESUBMIT -Indicate if fire sprinklers will need to be modified.
-Indicate if conveyors are interconnected to fire alarm and shut down during a general alarm.
john.vincent@tucsonaz.gov
5203495581
01/30/2024 PDSD Application Completeness Express REVIEW COMPLETED