Permit Number: TC-COM-0124-00184
Parcel: 14041867A

Address:
3350 E WESTCO PL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0124-00184
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/08/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 3/7/2024 5:04:40 PM
1. UNRESOLVED - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not
engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. This includes firms operating as sole proprietorships. To register, please fill out the form at the link below and mail it to
the State of Arizona Board of Technical Registration located at 1110 W. Washington Street, Suite 240, Phoenix, AZ 85007. https://btr.az.gov/sites/default/files/2022-10/firm_annual_registration_9.22.22.pdf



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/5/2024 12:07:58 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/6/2024 2:30:26 PM
1. General - Add to Cover Sheet The Conveyer System conforms to 2018 IBC Chapter 30 - Elevators and Conveying Systems - Section 3004 and ASME B20.1 - (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/5/2024 10:01:22 AM
Electrical Review of FedEx
By: Ron Ross PE
A2422-PER101: Comment only: 2, 3, and 5 Hp motors all seem to be overloaded for 480V motors.

A2422-PER401: Should have shown Panel PDP2 and indicate motor/vfd locations. Fortunately, Sheets ED1.3 and ED1.5 do show locations. If this information had not been provided, the electrical application would have been denied.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/7/2024 12:22:00 AM
Second Plumbing Review: No Plumbing Work shown
Resolved-1). Need to address Building Plan Review comment #1 -2018 IPC 403.1
03/04/2024 Fire New Construction REVIEW COMPLETED
03/01/2024 PDSD Application Completeness Express REVIEW COMPLETED