Permit Number: TC-COM-0124-00183
Parcel: 117042400

Address:
529 N 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00183
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/02/2024 External Reviewers - Willdan REQUIRES RESUBMIT Contact Bill McClellan by email at bmcclellan@willdan.com or cell (928) 580-3179 for review comment questions copy svasquez@willdan.com
1. Sheet A0.0 Clarify exit separation distance to meet 1007.1.1
2. Sheet A1.0 Need to identify all dimensions, fixtures and clearances work for accessible restroom to comply with details provided on sheet A4.0(BM)
3. Sheet A1.0 Clarify that existing egress doors and interior doors comply with ADA accessibility. Percentage of ADA upgrades are required for access to building per A117 section 201 & 2010 ADA standard 36.402 for alterations if needed. (BM)
4. Sheet A2.0 New addition area, Need to identify all insulation at roof, walls & floor to meet 2018 IECC C402 (BM)
5. Sheet A2.0 Provide framing detail for GB ceiling, not identified in architectural or structural plan details. IBC 107.2.1(BM)
6. Sheet A3.0 Wall finish at restroom will need to meet IBC 1209.2.2 (BM)
7. Sheet S0.0 Provide calculations for structural design of addition, incomplete in plan documents. IBC 107.2.1 (BM)
8. Sheet S0.0 Will need to provide special inspection form to identify items of inspection, incomplete in documents. IBC chapter 17(BM)
9. Sheet S0.0 All new mechanical equipment is identified on existing building roof structure. Will need to provide data / calculations that existing roof structure will support new equipment. Incomplete in plan documents IBC 107.2.1(BM)
10. Sheet E1.0 Provide existing Exit sign, EM lighting and egress EM light layout for existing building, incomplete IBC 107.2.1 (BM)
11. Sheet E2.0 Feeder size for 400 amps appears to not meet NEC Table 310.15(16) for 75 degree listed conductors connections to equipment. Clarify
02/27/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
01/31/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-0124-00183
529 North 6th Avenue – C-3
TI: Green Toes (1st Review)

TRANSMITTAL DATE: January 31, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

The site is in the C-3 zone (UDC 4.7.22). Personal Service is a permitted use in the C-3 zone.

1. The footprint of the addition proposed within TC-COM-0124-00183 does not match the footprint of the addition shown on issued DP15-0010. A revision to DP15-0100 will be required if the addition is proposed as presented.

If you have any questions about this review, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/26/2024 Fire New Construction REVIEW COMPLETED
01/30/2024 PDSD Application Completeness REVIEW COMPLETED