Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2024 Commercial Electrical APPROVED
02/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/12/2024 Commercial Building REQUIRES RESUBMIT submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
1. Please identify and label the bicycle rack on the Site Plan.
2. Please identify and label the mop/service sink in your Furniture, Fixtures & Equipment Plan. Reference: IBC Table 2902.1
3. Note 15 on Sheet P102 mentions a grease interceptor, please locate and label it in your drawings.
4. You show 2 indoor accessible seats in your seating calculation, however you show only one in your Life Safety Plan, please correct this.
5. Per previous issued Certificate of Occupancy document, this is occupancy type A-2 and type of construction VB/AS. Please correct his in your drawings.
6. Please resubmit.
02/15/2024 Commercial Mechanical REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all comments were addressed.

1. Amend plans to provide outdoor air ventilation calculations. IMC 401, 402, 403, Table 403.3.

2. Amend plans to provide the air-balance schedule IMC 403, 501.4.

3. Amend plans to provide detail for condensate drain termination IMC 307

Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
02/15/2024 Commercial Plumbing REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all comments were addressed.

1. Amend restroom plumbing fixture schedule to indicate Lavatories installed in all buildings shall be provided with automatic faucets dispensing a maximum of 0.25 gallon per metering cycle. Additionally, they should run for a minimum of 10 seconds. IPC as amended 419.6, ICC A117.1 606.4

2. Amend plans to specify tempered water for lavatories in public toilet facilities with Tempered water shall be delivered from lavatories and group wash fixtures located in public toilet facilities provided for customers, patrons and visitors. Tempered water shall be delivered through an approved water-temperature limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3.

3. Amend plans to provide a list of above and below ground, water supply and sanitary drainage piping materials to be used with this project section IPC 605, 702

4. Amend plans to provide supply service and meter sizing calculations - IPC 603

5. Amend plans to provide water supply piping sizing calculation - IPC 604

6. Amend plans to show detail of trap primer at floor drains. IPC 1002.4.1

Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
02/08/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
01/31/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T TC-COM-0124-00181
1209 W IRVINGTON RD. UNIT 150 – C-2
Food Service (1st Review)

TRANSMITTAL: January 31, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Food Service: Excluding Soup Kitchens is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. The drive thru expansion requires a development package. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/30/2024 Fire New Construction REVIEW COMPLETED
01/29/2024 PDSD Application Completeness REVIEW COMPLETED