Permit Number: TC-COM-0124-00181
Parcel: 137055200

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0124-00181
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2025 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT The construction drawings will have to be revised to eliminate the Drive-Thru Bump-Out prior to the removal of the special inspection requirements.as requested in the Structural Engineer's letter.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/22/2025 Water Sterilization Report (Deferred Submittal) Express REQUIRES RESUBMIT The required water disinfection report is incomplete. Your report should include the results of a bacteriological examination by a licensed testing laboratory of the water in the distribution system after the chlorine has been purged from the system. Section 610.1 of the 2018 International Plumbing Code describes the testing requirements.
04/21/2025 PDSD Application Completeness Express REVIEW COMPLETED