Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0124-00177
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/12/2024 | Commercial Electrical | REQUIRES RESUBMIT | TC-COM-0124-00177 After review of the updated changes and discussion with the building officials, we require the following steps be taken prior to approval. Remove reference to the 2017 NEC code reference for the interconnection method on Sheet E1.2. Replace with reference to the 2023 NEC code referenced 705.12(B)(6). File an appeal to the building official to use the 2023 NEC reference for the interconnection method. We will work to expedite the reviews once the appeal is filed and the plans are resubmitted with the updated reference. |
||
03/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |