Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0124-00161
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2024 | Commercial Plumbing | NOT REQUIRED | |||
| 03/05/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/26/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Ref; Lighting Plan. 1a. What is the note,” HIGH ENERGY BULB 4000K 32 VA/FIX” associated with? 1b. The Emergency interior lighting wall pack unit information is not shown anywhere in the lighting or power plans. What does the ‘B’ signify? Indicate wiring methods and detail about the unit. NEC art 700. 1c. Why do the Exit fixtures have a letter ‘a’ by them? Are they controlled by switch ‘a’? How are they wired? 1d. How are the exterior luminaires controlled? 2. Provide more detail in the panel schedule as to the location Room ‘A’ or ‘B’ for the electrical devices and Mechanical equipment. NEC art 408.4. 3. Provide GFI protected 120-volt receptacles for the rooftop AC Units. NEC 210. 4. Provide Tamper Resistant receptacles if applicable per NEC art 406.12. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 03/05/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. provide COMcheck envelope and mechanical compliance certificates). Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018. 2. Verify the scale of the mechanical roof plan. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018. 3. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 4. Tucson Preparatory School admits students 14 to 21 years of age. Revise the ventilation calculations using the Occupation Classification, “Education, Classrooms (age 9 +).” Reference: Section 403.3.1.1, IMC 2018. 5. Clarify how the ductwork will be installed (i.e. all ducts above the roof?) and how the return air will be ducted from the room back to the unit. Reference: Section 107.2.1, IBC 2018. |
||
| 02/27/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0124-00161 ADDRESS/PARCEL: (104 E PRINCE RD TUCSON, AZ 85705) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Sheet G0.0 Project Information, Parking is shown as N/A. Please provide parking information to include the parking required as a result of the 1,080 sf of additional building area. Show the total required and the provided parking. Please locate and identity the bicycle racks as well on the site plan. 2. Please provide a Site Plan. 3. Sheet G0.0 Code Plan indicates existing doors. Per aerial photograph, these doors are located where cars are parked. This should be labeled New door (not Existing)??? 4. Sheet G0.0 Project Information indicates Occupancy as E – Educational, no mention of fire sprinkler, please confirm this fire info. Please clarify and identify that this E occupancy is for the existing facility (on the existing 7,804 sf). At no sprinkler, allowable area at 9,500 sf (however, if it has automatic sprinkler the allowable area is 38,000 sf). Please confirm this information. 5. Sheet G0.0 Code Analysis, yes you can use 38,000 sf allowable area for the entire facility with E occupancy as the main classification assuming fire sprinkler is existing (identify this in your code analysis). Please correct me if I am wrong, you want to classify this addition as an accessory B occupancy to the Facility’s E group classification with Automatic Sprinklers(sprinkler submitted as a separate permit to Tucson fire). Hence the reason why you are proposing to post 49 occupant load. You may do this with the condition that you add a statement within your Code Analysis to this effect, “These two rooms are accessory to the main facility with 49 total occupant load for both Classroom A and B”. This to be posted in both rooms. Please coordinate & confirm these information for clarity within you code analysis. Keep the 54 occupant load calculation within your code analysis to illustrate the actual occupant load calculation. 6. Please re-submit. |
||
| 02/27/2024 | Site Engineering | REQUIRES RESUBMIT | See zoning comment | ||
| 02/13/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-0124-00161 - TD-DEV-0124-00019 104 E PRINCE RD. – C-2 Addition of two classrooms (1st Review) TRANSMITTAL DATE: February 13, 2024 Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Educational Use: Elementary and Secondary is a permitted use in this zone (Table 4.8-4). See Use-Specific Standard 4.9.3.D.1 – 7. 1. As Development Package (DP) TD-DEV-0124-00019 has not completed its first review Zoning cannot review the building plans for compliance with the DP. Zonin will review the building plans on the next submittal. Until the DP is approved by all review agencies Zoning cannot approve this building plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 02/21/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 01/26/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |