Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0124-00149
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/08/2024 | Commercial Building | APPROVED | |||
03/06/2024 | Commercial Electrical | APPROVED | |||
02/26/2024 | Site Zoning | APPROVED | |||
03/11/2024 | Water - PDSD | APPROVED | |||
03/11/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/11/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not resolved. The vents for the grease interceptor must rise vertically 6” above the flood rim prior to running horizontally. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018.] | ||
02/21/2024 | PDSD Application Completeness | REVIEW COMPLETED |