Permit Number: TC-COM-0124-00148
Parcel: 140411250

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0124-00148
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2024 Bldg Permits - Post Review REVIEW COMPLETED
03/26/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 3/22/2024 1:58:15 PM



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 3/22/2024 11:38:17 AM
The building review is approved. Subject to the field inspector's approval.




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/25/2024 4:55:02 PM
1. General - Provide Ventilation Calculation/Schedule - 2018 IMC Section Table 403.3.1.1 (RESOLVED)



Electrical(E) Reviewer (from previous submittal TUC9520001.012924)
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/30/2024 1:39:37 PM
Electrical Review of Tucson Commerce Center
By: Ron Ross PE
DMEP.1B Overall MEP Plan - Demolition: Could not locate Keyed Notes 3, 4, and 5.

E2.13B Overall / Enlarged Plan - Power: Could not locate Keyed Note 6.

E3.01B Electrical Schedules: RTU-3 and RTU-4 have undersized circuit breakers and conductors for the loads shown in Panelboard schedule. Should correct loads shown as Mechanical sheet M2.01B does show 70 amp Circuit breakers as correct. Should confirm, coordinate, and correct for IFC set.

If 70 amp Circuit Breakers need to be upsized, resubmit with properly sized conductors.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/23/2024 2:46:08 PM
Second Plumbing Review: OK
RERSOLVED-1). Need to address Bldg. plan review Comment 1 -2018 IPC 404.2
03/21/2024 PDSD Application Completeness REVIEW COMPLETED