Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2024 Commercial Electrical APPROVED
02/06/2024 Commercial Plumbing APPROVED
02/06/2024 Water - PDSD APPROVED
02/05/2024 Site Engineering NOT REQUIRED
02/07/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/07/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

1. Please verify and amend the Scope of Work or amend the Existing Floor Plan as the Rest Room is on the Existing Floor plan. IBC 107.2
2. Please provide a demo plan to include any concrete removal and trenching for plumbing if applicable IBC 107.2
3. Please amend plans to provide the type, size and spacing of the fasteners to be used at the wall to roof structure shown in detail 6/A4.0 IBC 107.2

4. Please amend plans to indicate if the Roof Top Unit (RTU) is a replacement for an existing RTU. If so, provide the weight of existing RTU to be removed and a comparison to the new RTU’s weight. If the new RTU weighs less than the existing, removed RTU all is good. However, if this is a new RTU or a replacement that is heavier than the removed unit, provide an engineering evaluation from an Arizona registered engineer to indicate the existing roof structure can support the new RTU to include calculations, plans/details for the support of such equipment. IBC 107.2

Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
02/06/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the beauty salon and no air from the beauty salon may be recirculated to any other space. HP-1 appears to be recirculating air from the beauty salon to the public restroom, break room, and to the reception room. Reference: Section 403.2.1 (3), IMC 2018.
2. Clarify the exhaust airflow rate. The Exhaust Fan Schedule calls for 500 CFM of exhaust but the mechanical floor plan calls out only 400 CFM of exhaust. Reference: Section 107.2.1, IBC 2018.
01/25/2024 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0124-00141
2547 E BROADWAY BL Zoning C-1

TRANSMITTAL DATE: December 5, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify the use, based on the last approved Development package the use is retail.