Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00131
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2024 Water - PDSD APPROVED
02/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide a grounding detail for the new electrical services.

2 Provide Arc fault protected branch circuits as required per NEC art 210.12.

3 Provide GFCI protection for the Laundry and Dishwasher per NEC 210.8(A), (D).

4 provide compliance with the 2918 IECC for the lighting as required per section R404.

5 What does ‘MW’ letters signify at the kitchen range location? Not shown in the electrical symbols legend.

6 The Site Electrical plan shows a new 600 amp service and the line diagram shows a 800 amp service. Please clarify.

7 The plumbing plan spec’s plan sheet ‘P-3.0’call out an electric hot water heater with a load rated at 4200watts and the unit electrical panel schedules call out a 2004 watts?. Please clarify.

8 Verify there is exterior illumination for the exterior side of the outdoor entrance as required per NEC art 210.70(A)(2). This will also be required for each unit.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
02/22/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Provide mechanical ventilation for the new dwelling units. Reference: Section R403.6, IECC 2018 and Section 403.3.2, IMC 2018.
2. Show the complete specifications for each air conditioner system, including the SEER2 for each system, the source of heat and the heating capacity. Reference: Section R103.2, IECC 2018.
3. Provide justification for installing HVAC units having total cooling capacities that exceed the total cooling loads shown in the submitted calculations and no heating capacity. Reference: Section R403.7 and R503.1.1.1, IECC 2018.
4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
5. If space is provided for the installation of a clothes dryer now or in the future (e.g. a stacked washer/dryer), the installation of an exhaust duct will be required. Reference: Section 504.8.6, IMC 2018.
6. Show the size, route and termination for all of the exhaust ducts. Show how the exhaust ducts are able to maintain the fire-resistance-rating of the floor-ceiling assemblies that they penetrate and the fire-resistance-rated demising walls in which they are located. Reference: Section 607.6, IMC 2018.
7. Clarify the locations of the condensing units (“exterior units”): are they ground-mounted or wall-mounted? Reference: Section 107.2.1, IBC 2018.
8. Clarify what appears to be two exhaust fans located in each bathroom in the new 1-bedroom dwelling units. Reference: Section 107.2.1, IBC 2018.
9. Clarify the balancing data for the proposed air conditioning systems in each new dwelling unit. The duct drawing calls for 350 CFM of supply and 600 CFM of return in each dwelling unit. The proposed air handlers are shown with 1600 CFM of supply. Reference: Section 107.2.1, IBC 2018.
02/22/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Label all pipe sizes on the waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.
2. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
3. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018
4. Provide the specifications and listing information for the proposed water heater. Show how the proposed water heaters and expansion tanks will fit withing the bottom cabinets in the new kitchens while maintaining access and working space. Reference: Sections 303.2, 501.4, and 501.5, IPC 2018 and Section 107.2.1, IBC 2018.
5. Show the size, route, and termination of the T&P relief pipe from each water heater. The drain from a pan located under a water heater shall terminate either to an indirect waste receptor or to the exterior of the building. Reference: Section 504, IPC 2018.
6. Revise the water distribution system design criteria to account for the actual static lift to the highest fixture and the inclusion of a reduced pressure backflow preventer. Reference: Section 604.1, IPC 2018, as amended by the City of Tucson.
7. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. automatic clothes washers). Reference: Section 604.9, IPC 2018
8. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks. Reference: Section 704.3, IPC 2018.
9. A plumbing vent may not be used for any purpose other than venting of the plumbing system. The waste riser diagram appears to show the third-floor waste piping only connected to the 3” vent, not to a waste pipe. Reference: Section 901.4, IPC 2018.
02/22/2024 Commercial Structural REQUIRES RESUBMIT TC-COM-0124-00131
SEPARATE 4 BEDROOM APARTMENTS TO (2) BDM AND (1) BDM APARTMENTS IN BUILDING #3 Unit 3101
Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Please amend plans to update Code review Type of Construction to reflect Table 601 and assign the fire-resistance rating requirements for building elements to complete Fire Protection table in place of the dashes. IBC 107.2.1
2. Please update Code Review, under Occupant Loads to indicate Building #3 in place of Building #12 and provide the occupant load for each unit type. IBC 107.2.1 For example, a 2-bedroom 870 sq ft unit would be 4.35 or 5 occupants and the 1-bedroom units 489 sq ft unit would be 2.44 or 3 occupants resulting in 96 occupants for all floors. IBC Chapter 10
3. Please amend the plans to provide a drawing and details for all new walls to include connection details. Additionally, provide construction drawings at new exterior doors to include, header size, required jack studs, trimmers, connection details and finishes at the new exterior doors IBC 107.2.1, IBC 107.2.7
4. Amend plans to provide and identify fire partition and the fire resistive rating as required by IBC420.2 Additionally, provide wall assembly section and connection details.
5. Amend plans to provide details for penetration firestops. Please show the entire assembly on the drawings. IBC 714.1
6. Amend plans to indicate what the space is between the new bathtub and the new shower. IBC107.2.1
Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
02/14/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
02/06/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-COM-0124-00131 - BLDG 3, TC-COM-0124-00132 - BLDG 6, TC-COM-0124-00133 - BLDG 8 & TC-COM-0124-00134 - BLDG 9 - TD-DEV-1123-00456
2550 W IRONWOOD HILL DR BLDG 3. – R-3
Convert 4 bedroom units to 2 bedroom units. (1st Review)

TRANSMITTAL DATE: February 6, 2024

Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-3 zone (UDC 4.7.12). Multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standard 4.9.7.B.6

1. The building plans have been reviewed for compliance with Development Package (DP) TD- TD-DEV-1123-00456 and all though it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/29/2024 Fire New Construction REVIEW COMPLETED
01/23/2024 PDSD Application Completeness Express REVIEW COMPLETED