Permit Number: TC-COM-0124-00125
Parcel: 11505046B

Address:
109 W GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00125
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2024 Commercial Mechanical APPROVED
02/21/2024 Commercial Structural APPROVED
01/23/2024 Site Zoning APPROVED
02/21/2024 Water - PDSD APPROVED
02/13/2024 Site Engineering NOT REQUIRED
02/21/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/20/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Plan sheet E-2.

1a. The notes In the ‘REFLECTED CEILING FLOOR PLAN (PARCIAL)’ shows the ‘INTERIOR LED A’, ‘B’, as existing and the ‘INTERIOR LIGHT FIXTURE LEGEND’ shows them as ‘NEW’. Please clarify in detail what is new and what is existing to remain. 2018 IBC section 107.2.1.

1b. Assign branch circuit numbers in the plan for lighting circuits. NEC 408.4.

2 Provide 120 volt receptacles in the meeting room in compliance with NEC art 210.71.

3 Provide compliance with the 2018 IECC for the interior lighting.

4 Provide exhaust fan controls in the electrical plan as indicated per Mechanical ‘EXHAUST FAN SCHEDULE’ plan sheet M-2.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC.
02/21/2024 Commercial Plumbing REQUIRES RESUBMIT Show the approximate location of the connection of the building sewer to the public sewer. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
01/23/2024 Fire New Construction REVIEW COMPLETED
01/22/2024 PDSD Application Completeness REVIEW COMPLETED