Permit Number: TC-COM-0124-00122
Parcel: 124050630

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-0124-00122
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2024 Commercial Plumbing APPROVED
06/24/2024 Water - PDSD APPROVED
06/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/24/2024 Commercial Mechanical REQUIRES RESUBMIT 1. The supplied literature only indicates that the Calrod heating elements have been listed. Verify any listing for use without a hood. [Initial comment: Show that the pretzel oven is listed for ventless operation per UL 710B (i.e. the appliance produces an effluent with less than 5 mg per cubic meter of grease when tested with an exhaust flowrate of 500 CFM) or install a Type I hood. Reference: Section 507.2, IMC 2018.]
2. No load calculations supplied. [Initial comment: Show that the heat and moisture loads from the proposed Unox oven (and the pretzel oven if it is listed per UL 710B) are included in the HVAC load calculations for the space or install a Type II hood over the oven(s). Reference: Section 507.3, IMC 2018.]
06/06/2024 PDSD Application Completeness REVIEW COMPLETED