Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0124-00122
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2024 | Site Zoning | APPROVED | |||
03/25/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/19/2024 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0124-00122 ADDRESS/PARCEL: (904 E UNIVERSITY BL TUCSON, AZ 85719) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Please submit detail drawings of the new countertop illustrating compliance that the facility is accessible complying to the ICC/ANSI A117.1 for both Employees and Customers. 2. If the soda bar seating is new, please provide detail drawings. 3. If the bench seating is new, please provide detail drawings. 4. Designate handicap accessible portion of the bench seating and the bar seating area. 5. On the Reference Floor Plan, label which equipment are new and which are existing. 6. Please submit Electrical Drawings. 7. Please submit Plumbing/Mechanical Drawings. 8. Within the Code Analysis, please clarify “occupants 1:500” and correct as necessary. 9. Within the Code Analysis, please clarify “toilet 1:750” and correct as necessary. 10. Within the Code Analysis, please clarify “lav 1:1” and correct as necessary. 11. You are proposing to use restroom facility 429 ft away. Please add a note below your service sink item within the Code Analysis reflecting what is shown in your Enlarged Location Map. 12. Please locate and label your service sink on your reference floor plan. 13. Please re-submit. |
||
03/19/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide an electrical floor plan and indicate the branch circuit and panel designation for each outlet and or equipment that correlates with the panel schedule. 2 The #8AWG conductors shown in the panel schedule for the 60 amp rated OCPD’s are undersized. Revise to #6AWG, NEC 310.15(B)(16), 75C column. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
03/25/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide a plumbing design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018 | ||
03/15/2024 | Fire New Construction | REVIEW COMPLETED | |||
03/05/2024 | PDSD Application Completeness | REVIEW COMPLETED |