Permit Number: TC-COM-0124-00122
Parcel: 124050630

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0124-00122
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2024 Commercial Building APPROVED
05/28/2024 Commercial Electrical APPROVED
06/03/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/03/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Show that the pretzel oven is listed for ventless operation per UL 710B (i.e. the appliance produces an effluent with less than 5 mg per cubic meter of grease when tested with an exhaust flowrate of 500 CFM) or install a Type I hood. Reference: Section 507.2, IMC 2018.
2. Show that the heat and moisture loads from the proposed Unox oven (and the pretzel oven if it is listed per UL 710B) are included in the HVAC load calculations for the space or install a Type II hood over the oven(s). Reference: Section 507.3, IMC 2018.
3. If no Type 1 or Type II hoods are required, provide general exhaust for the kitchen area, 0.70 CFM per square foot based on an area of 100 square feet per cooking appliance. Reference: Section 507.1 (2), IMC 2018.
06/03/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide direct connections to the sanitary waste system for the hand sinks. Reference: Sections 301.3 and 802.1, IPC 2018.
2. Provide third-party listing and material standards for all new plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018.
3. Appliances (e.g. beverage dispensers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
4. Verify the locations of the proposed indirect waste receptors (i.e. floor sinks) are visible for inspection and have ready access for cleaning. Reference: Section 802.4, IPC 2018.
5. Show how the new hand sinks will be vented. Reference: Section 901.2.1, IPC 2018.
6. A separate submittal to PC Industrial Wastewater Control is required to verify that the public sewer will be protected from harmful discharges (i.e. verify if a grease interceptor is needed). Contact Lucinda.Hyatt@pima.gov for review and assessment. Reference: Section 1003.1, IPC 2018
06/03/2024 Water - PDSD REQUIRES RESUBMIT Show the location and size of the water meter, backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018
05/15/2024 PDSD Application Completeness REVIEW COMPLETED