Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00115
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2024 Site Zoning APPROVED SAME CONSTRUCTION PLANS ON PERMITS: TC-COM-0124-00064 (5402 E 30TH ST Unit:BLDG C UNIT 8 TUCSON, AZ 85711), TC-COM-0124-00114 (5402 E 30TH ST Unit:BLDG C UNIT 9 TUCSON, AZ 85711), TC-COM-0124-00115 (5402 E 30TH ST Unit:BLDG C UNIT 10 TUCSON, AZ 85711) SPECS AND OTHER DOCS MAY DIFFER.
WITH SPECIFIC ADDRESSES ASSIGNED TO EACH SET
02/13/2024 Site Engineering NOT REQUIRED SAME CONSTRUCTION PLANS ON PERMITS: TC-COM-0124-00064 (5402 E 30TH ST Unit:BLDG C UNIT 8 TUCSON, AZ 85711), TC-COM-0124-00114 (5402 E 30TH ST Unit:BLDG C UNIT 9 TUCSON, AZ 85711), TC-COM-0124-00115 (5402 E 30TH ST Unit:BLDG C UNIT 10 TUCSON, AZ 85711) SPECS AND OTHER DOCS MAY DIFFER.
WITH SPECIFIC ADDRESSES ASSIGNED TO EACH SET
02/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT SAME CONSTRUCTION PLANS ON PERMITS: TC-COM-0124-00064 (5402 E 30TH ST Unit:BLDG C UNIT 8 TUCSON, AZ 85711), TC-COM-0124-00114 (5402 E 30TH ST Unit:BLDG C UNIT 9 TUCSON, AZ 85711), TC-COM-0124-00115 (5402 E 30TH ST Unit:BLDG C UNIT 10 TUCSON, AZ 85711) SPECS AND OTHER DOCS MAY DIFFER.
WITH SPECIFIC ADDRESSES ASSIGNED TO EACH SET
01/23/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 1/23/2024 12:13:29 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 1/23/2024 12:13:17 PM



Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 1/23/2024 12:13:23 PM



Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 1/23/2024 11:59:53 AM
1. General: Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance. Reference 2018 IECC Section 505.1.




Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 1/23/2024 12:12:04 PM
1. Sheet P1.0: The gas riser diagram does not indicate the design information required to complete a thorough review on the gas supply system. Provide the following information: lengths of gas piping from supply to outlets, inlet pressure,
Pressure drop and specific gravity used in the design of this system in accordance with the 2018 IFGC.
01/19/2024 Fire New Construction REVIEW COMPLETED SAME CONSTRUCTION PLANS ON PERMITS: TC-COM-0124-00064 (5402 E 30TH ST Unit:BLDG C UNIT 8 TUCSON, AZ 85711), TC-COM-0124-00114 (5402 E 30TH ST Unit:BLDG C UNIT 9 TUCSON, AZ 85711), TC-COM-0124-00115 (5402 E 30TH ST Unit:BLDG C UNIT 10 TUCSON, AZ 85711) SPECS AND OTHER DOCS MAY DIFFER.
WITH SPECIFIC ADDRESSES ASSIGNED TO EACH SET
01/19/2024 PDSD Application Completeness Express REVIEW COMPLETED