Permit Number: TC-COM-0124-00112
Parcel: 13804286A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0124-00112
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The line diagram Keynotes #11 states, "SECTION OF FEEDER (ITEM 10) TO BE REMOVED FROM SWITCHGEAR AND CONNECTED TO NEW DISCONNECT SWITCH. (ITEM 8). Are you sure you want the existing feeder and the New Meter both connected to the New Disconnect? Please clarify.

2 Provide for a grounding electrode system to be connected to Panel ‘A’ at the School Building if not already installed. NEC art 250.32.

Ref;2018 IBC section 107.2.1, 2017 NEC.