Permit Number: TC-COM-0124-00099
Parcel: 12806255A

Address:
5921 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0124-00099
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2024 Site Zoning APPROVED
01/24/2024 Site Engineering NOT REQUIRED
02/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/02/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please note: These plans were incomplete and additional comment may arise after comments have been addressed.

1.Amend plans to include the designer’s seal, signature, and date signed on all sheets 107.1

2.Amend plans to add a list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1

2a. These plans must be sealed by a design professional registered in the State of Arizona IBC 107.1

2b.Please provide code analysis to include the following;

2c.Occupancy Group, for example B,M or? IBC 302.1

2d.Construction Type, For example VB IBC 602.1

2e.Fire Sprinklers Yes or No IBC 107.2.1

2f. List total occupant load IBC 1004.1

2g. Indicate the number of exits required and provided. IBC 107.2.3

2h. Indicate the number of restrooms required and provided IBC Chapter 29

3.Amend plans to provide a dimensioned floor plan with door widths indicated. IBC 107.2.1

3a. Show doors swinging in the direction of egress travel. IBC 1010.1.2.1

4.Amend plans to ensure the occupancy classification(s) are shown. IBC 302.1

5.Amend plans to provide the total number of occupants for the floor. IBC 107.2.3

6.Amend the plans to ensure the number of occupants is shown for every room and space. IBC 107.2.3

7.Amend the plans to show the occupant load factor and area for every room and space. IBC 1004.5

8.Amend plans to show exit signs are at doors, and as required to direct egress. IBC 1013.1

9. Amend plans to note or otherwise indicate: Only the main door uses the key lock option with the correct sign stating: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. IBC 1010.1.9.4

10. Please show sales counter, if used and show as accessible. 1109.12.3

11. Amend plans to show location and method of providing emergency egress lighting and power source that will provide power for a minimum of 90 minutes. IBC 1008

12. Please amend plans to provide an electrical plan to include the following: IBC 107.2.1

12a. Power floor plan showing receptacles, switches, outlets, etc., sink locations and circuiting identified.

12b. GFCI protection is required for any receptacle within 6 feet of a sink. This is for any receptacle within 6-foot of sink, not just counter receptacles.

12c. Lighting floor plan including fixture types & wattage with circuiting identified.

13.Provide mechanical plans to include the following information; IBC 107.2.1

13a.Layout of ductwork, A/C units, air-handlers, diffusers, etc. IMC 303, 304, 306, 308,

309, 603.

13b. Outside ventilation air calculations IMC 401, 402, 403, Table 403.3.

13c. Toilet room exhaust ventilation systems IMC 501.2, 501.3.





Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
01/19/2024 Fire New Construction REVIEW COMPLETED
01/18/2024 PDSD Application Completeness REVIEW COMPLETED