Permit Number: TC-COM-0124-00096
Parcel: 10821324B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0124-00096
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2024 Site Zoning APPROVED
02/16/2024 Fire New Construction NOT REQUIRED
02/27/2024 Site Engineering NOT REQUIRED
03/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/04/2024 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
1. Thank You for submitting the Structural Engineer's field observation.
2. Please submit a complete set of drawings illustrating the fixes being proposed generated by Arizona Licenses Architect along with his seal/signature/date on all the drawings sheets. This should reflect all of the structural engineer's recommendations as well as the areas drywall are being replaced, mechanical, electrical, etc.
3. Please do make sure to re-submit a complete set of documents including the structural engineer's field report & recommendations.
4. Please re-submit.
01/29/2024 PDSD Application Completeness REVIEW COMPLETED