Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0124-00084
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2024 | Commercial Electrical | APPROVED | |||
| 02/20/2024 | Commercial Mechanical | APPROVED | |||
| 01/17/2024 | Site Zoning | APPROVED | |||
| 02/09/2024 | Site Engineering | NOT REQUIRED | |||
| 02/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/20/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The replacement of a lavatory in a public restroom will result in the lavatory requiring the installation of a metering faucet. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide tempered water for the lavatories in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g. 24” for a ½” HW supply). |
||
| 02/20/2024 | Commercial Structural | REQUIRES RESUBMIT | Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. 1. Provide drawings at service counters illustrating the required height and width for accessibility (for both customers and employees) per ANSI A117.1 section 904. 2. Restrooms: Other fixtures not allowed within the required clearance for the water closet per ANSI A117.1 figure 604.3, please correct this condition. 3. Please resubmit. |
||
| 01/31/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 01/17/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |