Permit Number: TC-COM-0124-00079
Parcel: 12306044A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00079
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2024 Site Zoning APPROVED
02/08/2024 Site Engineering NOT REQUIRED
02/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/09/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

Please provide accessible route from an accessible building entrance to primary function areas. IEBC 305.4.3 Further, provide dimension of the opening from the Lobby to the Patient area. Keep in mind 2009 ICC A117.1 403.5 would require a clear width of 36” with an exception to reduce the clear width to 32”

Please amend plans to show the Exit Sign locations on the plan where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that any point in an exit access corridor or exit passageway is within 100 feet or the listed viewing distance of the sign, whichever is less, from the nearest visible exit sign. IBC 1013.1

Please indicate how the Exit Signs are to be illuminated. IBC 1013.3

Please amend plans to show the location and method of emergency means of egress illumination for entire path of egress travel. IBC 1008.1

Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
01/23/2024 Fire New Construction REVIEW COMPLETED
01/17/2024 PDSD Application Completeness Express REVIEW COMPLETED