Permit Number: TC-COM-0124-00074
Parcel: 12902091E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00074
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2024 Site Zoning APPROVED
01/30/2024 Site Engineering NOT REQUIRED
01/31/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/31/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
This is a commercial project. Provide electrical plans showing all electrical work required for the installation of the washer/dryer, sealed by an Arizona Registrant. Reference: 2018 IBC Sections 107.1 and 107.2.1,
2017 NEC, 2018 IECC, City of Tucson Commercial Plan/Permit Submittal Requirements. and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
01/30/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Provide calculations to verify that adequate ventilation will be provided for the hair salon. Reference: Section 403.3.1.1, IMC 2018.
2. Provide a mechanical design to show the required ventilation and exhaust for the hair salon. Reference: Section 107.2.1, IBC 2018.
3. The building has 2 stories. Show how and where the proposed dryer vent will be terminated. Reference: Section 504.4, IMC 2018.
01/30/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide the third-party listing information for the salon backwash fixtures. Reference: Section 303.4, IPC 2018.
2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
3. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g. 24 inches for ½” HW supply, 6 inches for ¾” HW supply).
5. Provide a vent for the lavatory, P-1. Reference: Section 901.2.1, IPC 2018.
6. Clarify the location of the vent for the south salon backwash. It cannot utilize the common vent serving the clothes washer and the sink, P-3. Reference: Section 911.3, IPC 2018.
7. The maximum vertical distance from the fixture outlet to the weir of the trap is 24 inches. Verify that the salon backwashes comply with this requirement. Reference: Section 1002.1, IPC 2018.
01/30/2024 Commercial Structural REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
Space from Office to Hair Salon
1. A complete Code Analysis required (this will is crucial to be able to issue a new certificate of occupancy).
2. Show on the site plan the location of the handicap stall(s) and striped accessible route to the front door.
3. Show/complete the front half layout of the space and indicate what they are.
4. Sink is in the required clear opening for wheelchair access.
5. Show the 5 ft radius required by ICC/ANSI A117.1
6. Confirm the door clear opening of 32 inches
7. Show the grab bars
8. Confirm that the air diffusers and return grill are to remain in their current location, if they are relocated....provide a reflected ceiling plan to illustrate.
9. Electrical drawings missing, please submit.
10. Show/indicate on the drawing the location of the illuminated exist sign as well as the emergency lights and confirm they have battery backup and the fire extinguisher.
11. Confirm whether you have fire sprinkler or not.
12. Please resubmit
01/23/2024 Fire New Construction REVIEW COMPLETED
01/11/2024 PDSD Application Completeness REVIEW COMPLETED