Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0124-00025
Parcel: 12909146C

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0124-00025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/08/2024 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-0124-00025 (1930 E SILVERLAKE RD TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The submitted site plan needs to show the address of the permit and the location of the repairs being made, 2018 IBC section 105.3.
2. Make a notation on the plans if the repairs will be like-for-like, 2018 IBC section 107.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/05/2024 PDSD Application Completeness REVIEW COMPLETED