Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0124-00019
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/01/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 2/29/2024 2:26:31 PM 1) Resolved - General: Include the correct risk category per 2018 IBC section 1604.5 and window uplift and pressure meeting the requirements of the amended 2018 IBC sections 1609.5.1.1 #1 (110 mph wind) and #2.3 (35 psf) on the drawings and structural calculations. Please revise all affected sheets and calculations. 2) Unresolved - Sheet S1.0: Provide the geotechnical engineer report for the soil bearing capacity referenced in the Foundation notes #1. (2018 IBC section 1803) Not provided. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 2/29/2024 2:23:30 PM Building review is approved. Subject to the field inspector's approval. Mechanical N/A Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Approved Reason: Date Completed : 1/16/2024 4:58:46 PM The electrical review is approved. Subject to the field inspector's approval. Plumbing N/A |
||
02/21/2024 | PDSD Application Completeness | REVIEW COMPLETED |