Permit Number: TC-COM-0124-00014
Parcel: 105110490

Address:
4646 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0124-00014
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/18/2024 5:17:44 PM
GENERAL - DEFERRED SUBMITTAL REQUIREMENTS: The engineer of record has stated that design of the prefabricated wood trusses and prefabricated sun shades/canopies shall be accomplished via Deferred Submittal. Please note that IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official. The IBC further requires the following procedure be followed when permitting deferred submittals:

1. All submittals shall first be reviewed by design professional in responsible charge.

2. Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.

3. They shall then be submitted for review by the building official.

4. No structural elements shall be installed until approved by building official.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/14/2024 10:53:36 AM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/11/2024 12:06:18 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/12/2024 9:55:44 AM
Electrical Review of Car Wash
By: Ron Ross PE
E2.1 CONDUIT PLAN: Could not locate Keynotes 10 and 14.
E2.2 CARWASH EQUIPMENT CONNECTION PLAN: Could not locate Keynote 3.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 3/16/2024 11:51:35 AM
Second Plumbing Review: Comments 4, 6, 8 Remain
Resolved-1). Add sidewall to fixture center measurements to plan page A7.2 -IPC 2018, 404.2, 405.3.1

Resolved-2). Gas Piping Material not selected on plan page P5.0 -IFGC 2018, 403.1

Resolved-3). Add Gas system legnth & sizing table used to gas load summary on plan page P5.1 -IFGC 402.3

Un-resolved-4). Dedicated Car wash water line on plan pages P1.1 P3.0, P4.3 is missing it's required RPZ Backflow. Add the the required backflow on the car wash dedicated water line at a point beyond any other connections. -2018 IPC 608.1, 608.3

Resolved-5). Plumbing plans only show one roof drain/overflow plan page A4.0 shows 2? Plan pages need to correlate. -IPC
2018, 106.3.1

Un-resolved-6). Toilets on plan page P3.0 are not vented properly-IPC 2018, 901.2.1, 912.1

Resolved-7). add fixture branch sizes to plan page P3.0 -IPC 2018, 604.1

8). Plan page P1.1 Primary/overflow Roof drain near restrooms is missing the square foot/GPM load & pipe sizing indicators. Provide this information on plan page P1.1 according to -2018 IPC 1106.2
04/09/2024 Site Engineering REQUIRES RESUBMIT 1. The building permit cannot be approved until the associated development package, TD-DEV-1223-00492, has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
04/12/2024 Site Zoning REQUIRES RESUBMIT FROM: Nathan Herrera
PDSD Zoning Review Section

PROJECT: TC-COM-0124-00014
4646 N ORACLE RD Zoning C-3
New car wash

TRANSMITTAL DATE:‎ April 12, 2024


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning has reviewed the building plan for compliance with the unapproved TD-DEV-1223-00492, Zoning cannot approve the building plans until the DP is approved.

COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. The building plans must match what is on the approved Development Package to be approved.

If you have any questions about this transmittal, Contact Nathan Herrera at Nathan.Herrera@tucsonaz.gov
04/11/2024 Water - PDSD REQUIRES RESUBMIT Show size of the proposed water meter, and the location and size of the backflow preventer on a site plan. [Initial comment: Show the location and size of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Typically, water meters are located at the property line, not within a building. Contact Tim Rowe at Tucson Water (tim.rowe@tucsonaz.gov) for assistance. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
03/13/2024 PDSD Application Completeness Express REVIEW COMPLETED