Permit Number: TC-COM-0124-00014
Parcel: 105110490

Address:
4646 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0124-00014
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/31/2025 5:13:27 PM
08/04/2025 Outdoor Lighting Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/31/2025 5:13:27 PM
08/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/04/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/3/2025 3:21:45 PM
Second Revised Plan Plumbing Review: Comment 1 Remains
Un-resolved 1). Plan Page P4.12, P5.0: Missing Sand/oil separator Sizing calculations. Add Sand/oil separator Sizing
calculations. -2018 IPC 103.4.2.2 **Please add calculations to the actual plan set not just response comments**
07/30/2025 PDSD Application Completeness Express REVIEW COMPLETED