Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0124-00014
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 7/31/2025 5:13:27 PM |
||
| 08/04/2025 | Outdoor Lighting Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 7/31/2025 5:13:27 PM |
||
| 08/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/04/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 8/3/2025 3:21:45 PM Second Revised Plan Plumbing Review: Comment 1 Remains Un-resolved 1). Plan Page P4.12, P5.0: Missing Sand/oil separator Sizing calculations. Add Sand/oil separator Sizing calculations. -2018 IPC 103.4.2.2 **Please add calculations to the actual plan set not just response comments** |
||
| 07/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |