Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0124-00014
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 6/30/2025 10:08:07 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 6/30/2025 1:12:45 PM |
||
| 07/01/2025 | Commercial Mechanical Standard | APPROVED | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved with Comments Reason: Date Completed : 6/30/2025 11:39:26 AM No Mechanical work noted for Revision on CB3, CB4, or CB5 Write Up. |
||
| 07/18/2025 | Site Engineering Standard | APPROVED | |||
| 07/16/2025 | Site Zoning Standard | APPROVED | Associated DP TD-DEV-1223-00492 approved | ||
| 07/14/2025 | Water - PDSD Standard | APPROVED | |||
| 07/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/01/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 6/26/2025 11:16:02 AM E6.0 LIGHT FIXTURE SCHEDULE: Need to provide an updated interior lighting Comcheck and an updated Exterior Tucson City Lumens/acre calculation to show continued compliance to Tucson City requirements as the lighting schedule has changed. |
||
| 07/01/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 6/29/2025 2:16:14 PM Revised Plan Plumbing Review: 1). Plan Page P4.12, P5.0: Missing Sand/oil separator Sizing calculations. Add Sand/oil separator Sizing calculations. -2018 IPC 103.4.2.2 |
||
| 07/01/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 6/26/2025 11:16:02 AM E6.0 LIGHT FIXTURE SCHEDULE: Need to provide an updated interior lighting Comcheck and an updated Exterior Tucson City Lumens/acre calculation to show continued compliance to Tucson City requirements as the lighting schedule has changed. |
||
| 07/14/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 06/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |