Permit Number: TC-COM-0124-00014
Parcel: 105110490

Address:
4646 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00014
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 6/30/2025 10:08:07 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/30/2025 1:12:45 PM
07/01/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved with Comments
Reason:
Date Completed : 6/30/2025 11:39:26 AM
No Mechanical work noted for Revision on CB3, CB4, or CB5 Write Up.
07/18/2025 Site Engineering Standard APPROVED
07/16/2025 Site Zoning Standard APPROVED Associated DP TD-DEV-1223-00492 approved
07/14/2025 Water - PDSD Standard APPROVED
07/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/01/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 6/26/2025 11:16:02 AM
E6.0 LIGHT FIXTURE SCHEDULE: Need to provide an updated interior lighting Comcheck and an updated Exterior Tucson
City Lumens/acre calculation to show continued compliance to Tucson City requirements as the lighting schedule has
changed.
07/01/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2025 2:16:14 PM
Revised Plan Plumbing Review:
1). Plan Page P4.12, P5.0: Missing Sand/oil separator Sizing calculations. Add Sand/oil separator Sizing calculations. -2018
IPC 103.4.2.2
07/01/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 6/26/2025 11:16:02 AM
E6.0 LIGHT FIXTURE SCHEDULE: Need to provide an updated interior lighting Comcheck and an updated Exterior Tucson
City Lumens/acre calculation to show continued compliance to Tucson City requirements as the lighting schedule has
changed.
07/14/2025 Fire New Construction Standard REVIEW COMPLETED
06/23/2025 PDSD Application Completeness Express REVIEW COMPLETED