Permit Number: TC-COM-0124-00005
Parcel: 11808046A

Address:
897 W 24TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0124-00005
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/11/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Provide a site plan showing the location of all the electrical equipment to be replaced.

2, Per the project description entered. Does “one on one” replacement also mean ‘Like for Like’? If the scope of work requires any design changes or calculations, or if any of the equipment ratings exceed 400 amps a complete set of sealed electrical plans will be required.

3. Provide a detailed description on the electrical site plan of all electrical conduit, conductors and equipment being replaced. Provide manufactures cut sheets and specifications for the 75KVA ‘Transformer’, ‘Main Control Cabinet’, or any electrical service equipment, including complete electrical line diagrams if applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
01/03/2024 PDSD Application Completeness Express REVIEW COMPLETED