Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0124-00005
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide a site plan showing the location of all the electrical equipment to be replaced. 2, Per the project description entered. Does “one on one” replacement also mean ‘Like for Like’? If the scope of work requires any design changes or calculations, or if any of the equipment ratings exceed 400 amps a complete set of sealed electrical plans will be required. 3. Provide a detailed description on the electrical site plan of all electrical conduit, conductors and equipment being replaced. Provide manufactures cut sheets and specifications for the 75KVA ‘Transformer’, ‘Main Control Cabinet’, or any electrical service equipment, including complete electrical line diagrams if applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 01/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |