Permit Number: TC-COM-0124-00004
Parcel: 11107024B

Address:
3333 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00004
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2024 Water - PDSD APPROVED
01/31/2024 Site Engineering NOT REQUIRED
01/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/11/2024 External Reviewers - Willdan REQUIRES RESUBMIT Contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179 for review comment questions CC svasquez@willdan.com
1. Sheet a1.07 Existing doors will need to identify hardware for new occupancy to meet 1010.1.10 & 1010.1.9.4(2). Also all handles will need to meet ADA requirements. (BM)
2. Sheet a2.01 landings at all doors will need to be identified to meet 1010.1.5 & 1010.1.6. One or more Egress doors will need to provide an accessible route to the public way per 1009.1. Not clear on plans (BM)
3. Sheet a2.01 Doors identified with keynote 8 will need all hardware removed and noted as not an ext for exterior side. Verify with AHJ (BM)
4. Sheet a2.02 Railing will need to be identified at entry with elevation change greater than 6" per IBC 1012.8 (BM)
5. Sheet e1.0 Identify dedicated clear work space for panel "B" per NEC 110.26, not clear with double door stile (BM)
6. Sheet e1.0 Service location and identification do not match one line diagram. Also panel B is identified in utility closet. Correctly identify all panels and service disconnects. Also identify if SES is new or existing. IBC 107.2.1 (BM)
7. Sheet M1 Provide calculation for all windows and doors to remain open while building is occupied to meet requirement or provide mechanical ventilation per IMC 403.2 (BM)
8. Sheet M1 Provide dimensions for roof tops that new (DCU) will be a min 10' or greater from edge of roof to meet IMC 304.11 (BM)
01/16/2024 Fire New Construction REQUIRES RESUBMIT Address Willdan comments. Questions: patricia.shelton@tucsonaz.gov
01/04/2024 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0124-00004
3333 E GRANT RD Zoning C-1
Change of Use, Interior remodel

TRANSMITTAL DATE:‎January 4, 2024


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0923-00384, Zoning cannot approve the building plans until the DP is approved.
2.COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.
.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/04/2024 PDSD Application Completeness Express REVIEW COMPLETED