Permit Number: TC-COM-0124-00004
Parcel: 11107024B

Address:
3333 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0124-00004
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2025 Commercial Mechanical Standard APPROVED
05/29/2025 Outdoor Lighting Standard APPROVED
06/10/2025 Site Zoning Standard APPROVED
06/09/2025 Water - PDSD Standard APPROVED
06/18/2025 Site Engineering Standard NOT REQUIRED
06/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/10/2025 Commercial Building Standard REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179 all applicable comments followed by the initials (BM)
1. Sheet g1.00 Building section identified as existing to remain has not been identified in code analysis for occupancy or occupant load. Clarify 2018 IBC 107.2.1 (BM)
2. Sheet g1.00 Revision letter note #2, states food no longer served, clarify A2 occupancy identified as open dinning 2018 IBC 303.3 & table 2902.1 for required plumbing fixtures. (BM)
3. Sheet d1.00 Clarify note for NW building section noted for existing walls to removed. Other plan notes identify existing to remain. 2018 IBC 107.2.1 (BM)
4. Sheet a1.01 Revision letter note #2 states food no longer being served. serving kitchen is still identified on plans. Clarify 2018 IBC 107.2.1 (BM) Note: grease interceptor noted to be removed for no food served.
5. Sheet a2.01 Per prior approval red-line notes on plan sheet a1.01, identify ramp slope and handrail to comply IBC 1012.2 & 1012.8 (BM)
06/10/2025 Commercial Electrical Standard REQUIRES RESUBMIT 1. Sheet e2.0 Exit sign and EM egress light fixtures are still identified above removed door. Remove from plan. 2018 IBC 107.2.1 (BM)
06/10/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet P0 Rear building section is noted on plan sheets for existing to remain. Plumbing demo plan still identifies existing fixtures to be removed and capped. Clarify 2018 IBC 107.2.1 (BM)
06/03/2025 Fire New Construction Standard REVIEW COMPLETED Fire alarm monitoring of the fire sprinklers back flow preventer valves shall comply with section 903.4 and 903.41 of the 2018 IFC.
fire extinguishers types and amount shall comply with section 906 of the 2018 IFC.
If equipped with kitchen hoods; Fire suppression requires a separate permit.
CO2 systems requires an operational permit.
05/16/2025 PDSD Application Completeness Express REVIEW COMPLETED